• name: GH11 6kva/10kva
  • 产品编号: B002
  • Input voltage range: 110V~290V AC(half load)
  • Output voltage range: 208/220/230/240VAC ± 1%
  • power factor: ≧0.99 @ Nominall Voltage (100% load)
  • Power efficiency: 0.8(0.9 customized)
  • waveform: Pure sine wave
  • Transfer time: 0ms
  • Views : 512

•True double-conversion on line UPS
•DSP technology guarantees high performance
•Output power factor 0.8(0.9 optional)
•Standard backup UPS and long backup UPS in one integrated unit
•Adjustable battery number from 16 pcs to 20 pcs
•Adjustable charging current via LCD or software (0.5A~6A)
•Wide input voltage range (110-300 VAC)
•Active input power factor correction 0.99
•50Hz/60Hz frequency converter mode
•Emergency power off function (EPO)
•3-stage extendable charging design for optimized battery performance
•Maintenance bypass available
•SNMP/USB/RS-232 communications
 

 

MODEL GH11- 6K(L) GH11-10K(L)
PHASE 1 phase in / 1 phase out
CAPACITY 6000 VA / 4800 W 10000 VA / 8000 W
INPUT
Nominal Voltage  208/220/230/240VAC
Voltage Range Low Line Loss 110 VAC ± 3% at 50% Load
176 VAC ± 3% at 100% Load
Low Line Comeback 120 VAC ± 3% at 50% Load
186 VAC ± 3% at 100% Load
High Line Loss 300 VAC ± 3%
High Line Comeback 290 VAC ± 3%
Frequency Range 46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz
Power Factor  0.99  @ 100% load
OUTPUT
Nominal Voltage  208/220/230/240VAC
AC Voltage Regulation  ± 1%
Frequency Range 
(Synchronized Range)
46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion  3 % THD (Linear Load)  
 6 % THD (Non-linear Load)
Transfer Time
(Line mode)
Bypass to Inverter Zero
Inverter to Bypass  Zero
Waveform (Batt. Mode) Pure Sinewave
EFFICIENCY
Line Mode 0.89 0.9
Battery Mode 0.88 0.89
BATTERY
Standard Model Battery Type 12 V / 7 AH 12 V / 9 AH
Numbers 16 16
Typical Recharge Time 9 hours recover to 90% capacity
Charging Current  Default:1.0 A ±  10%, 
Max.:2.0A ±  10%
Default:1.0 A ±  10%, 
Max.:2.0A ±  10%
Float Charging Voltage  218.4 VDC ±  1%
Long-run Model Battery Type Depending on applications
Numbers 16-20pcs(adjustable)
Charging Current  Default:4.0 A ±  10%,  
Max.:6.0A ±  10%
Default:4.0 A ±  10%, 
 Max.:6.0A ±  10%
Float Charging Voltage  273 VDC ±  1% (based on 20 pcs batteries)
INDICATORS
LCD Panel UPS status, Load level, Battery level, Input/Output voltage, 
Discharge timer, and Fault conditions
ALARM
Battery Mode Sounding every 4 seconds
Overload Sounding twice every second
Fault Continuously sounding
PHYSICAL
Standard Model Dimension 369 x 190 x 688 442 x 190 x 688
Net Weight (kgs) 61 75
Long-run Model Dimension 369 x 190 x 318 442 x 190 x 318
Net Weight (kgs) 12 18
ENVIRONMENT
Operation Humidity 0-95 % RH @ 0- 40°C (non-condensing)
Noise Level Less than 55dBA @ 1 Meter Less than 58dBA @ 1 Meter
MANAGEMENT
Smart RS-232/USB Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8,
 Linux, Unix, and MAC
Optional SNMP Power management from SNMP manager and web browser
*Product specifications are subject to change without further notice

download attachments : GH11 6-10KVA user manual 【查看】

 
Title:
 
Message:
* Entered characters:0 Word
Less than or equal500Character
Your mailbox:
*
Example: example@mail.com
Phone number:
 
By the number, "+", the horizontal bar "-", the maximum allowed 20 characters
Verification code:
   
400-000-000

在线客服

服务时段:9:00--18:00

扫一扫,马上浏览