• name: GL33 10kva~120kva
  • 产品编号: B010
  • Input voltage range: 305VAC ~ 460VAC
  • Output voltage range: 3 x 380VAC/400VAC (3Ph + N) ,Stationary: ±1% ; Transitory: ±5%
  • power factor: 0.6~1 (inductive or capacitive)
  • Power efficiency: >90%
  • waveform: pure sine wave
  • Transfer time: 0ms
  • Views : 397

  • Online double-conversion
  • DSP technology guarantees high reliability
  • True galvanic isolation transformer design
  • Control designed to withstand all kinds of loads
  • Intelligent battery management to prolong battery lifecycle
  • Redundant fan design and independent ventilation enhance durable operation under harsh environment
  • Adjustable battery numbers
  • Accept dual-mains input
  • Parallel operation with up to 4 units (option)
  • Variety of communication options available
  • Optional 7"touch LCD

     

 

Model GL33 10K GL33 15K GL33 20K GL33 30K GL33 40K GL33 60K GL33 80K GL33 100K GL33 120K
CAPACITY 10KVA/8KW 15KVA/12KW 20KVA/16KW 30KVA/24KW 40KVA/32KW 60KVA/48KW 80KVA/64KW 100KVA/80KW 120KVA/96KW
INPUT
Nominal Voltage 3 x 380VAC/400VAC (3Ph + N)
Acceptable Voltage Range 305VAC ~ 460VAC
Frequency 50/60 Hz ± 10 %
INVERTER
Nominal Voltage 3 x 380VAC/400VAC (3Ph + N)
Precision Stationary: ±1% ; Transitory: ±5% (load variations 100-0-100%)
Frequency 50/60 Hz synchronised ±1 % With mains absent ±0.1 Hz
Max.Synchronisation Speed ±1 Hz/s
Waveform Pure Sinewave

Total Harmonic Distortion 

(THDv)

< 2% (Linear Load) ; < 5% (Non-linear Load)
Phase Displacement 120º ±1% (balanced load) ; 120º ±2% (imbalances 50% of the load)
Dynamic Recovery Time 3 cycles at 98 % of the static value
Admissible Overload 110% for 10min; 150% for 60sec ; >160% for 200ms
Admissible Crest Factor 3:1
Admissible Power Factor 0.6~1 (inductive or capacitive)

Imbalance Output Voltage 

@ 100% Unbalanced Load

<1%
Current Limit High overload, short-circuit: RMS Voltage Limit ; High Crest-Factor current: Peak Voltage Limit
STATIC BYPASS
Type Solid state
Voltage 3 x 380VAC/400VAC (3Ph + N)
Frequency 50/60 Hz
Activation Criterion Microprocessor control
Transfer Time Zero
Admissible Overload 150% for 1 hour; 180% for 30sec; >200% for 200ms
Transfer to Bypass Immediate, for overloads above 160%
Retransfer Automatic after alarm clear
MAINTENANCE BYPASS
Type Without interruption
Voltage 3 x 400V (3Ph + N)
Frequency 50/60 Hz

Overall Efficiency

(Line mode)

Line Mode 90% 91% 92% 93%
Battery Mode 90% 91% 93% 93%
BATTERY & CHARGER
Battery Type and Numbers 12VDC x 32 pcs (29~32 pcs adjustable)
Nominal Battery Voltage 384 VDC (Based on 32pcs batteries)
Charging Method CC/CV
Charging Current Default 10A,Max.=Capacity/Battery Voltage Default: 10A. Max. 40A
Charging Voltage 432 VDC (Based on 32pcs batteries)
PHYSICAL
Dimension
D*W*H (mm)
656*405*817 656*405*941 821*432*1159 975*554*1286 975*635*1326
Net Weight (kgs) 118 120 179 241 278 400 471 573 650

download attachments : GL33 10-120kva user manual 【查看】

 
Title:
 
Message:
* Entered characters:0 Word
Less than or equal500Character
Your mailbox:
*
Example: example@mail.com
Phone number:
 
By the number, "+", the horizontal bar "-", the maximum allowed 20 characters
Verification code:
   
400-000-000

在线客服

服务时段:9:00--18:00

扫一扫,马上浏览